Aknan Group

Fire Safety Design for Warehouses and Industrial Facilities in Saudi Arabia: Storage, Sprinklers and Approvals

Fire Safety Design for Warehouses and Industrial Facilities in Saudi Arabia: Storage, Sprinklers and Approvals

A warehouse can be built exactly to its approved drawings and still be unsafe on the day it opens. The reason is simple. In storage and industrial buildings, the fire risk depends less on the building itself than on what is stored in it, how high it is stacked and how it is arranged. A sprinkler system designed for cartons of tinned food on low shelving may be overwhelmed by plastic goods in tall racking. When the use changes and the fire protection does not, the gap can be large.

Fire safety design for warehouses and industrial facilities in Saudi Arabia therefore starts with a question that owners sometimes cannot answer at design stage: what exactly will be stored here, and how?

Why storage drives the design

Commodity classification

Fire codes based on international models, including the Saudi Fire Code (SBC 801), classify stored goods according to how readily they burn and how much heat they release. Commodities range from non-combustible products on wooden pallets through progressively more hazardous classes, with certain plastics, aerosols, flammable liquids and similar materials treated as high-hazard. Packaging matters as much as the product: a non-combustible item in plastic wrapping on plastic pallets behaves very differently from the same item in a cardboard box.

Storage height and arrangement

The height of storage and the way it is arranged, whether in solid piles, on shelves, in palletised stacks or in racks, strongly influence how fast a fire grows and how hard it is to control. Above certain storage heights, the code treats storage as high-piled combustible storage, which brings additional requirements for fire protection, fire service access and smoke and heat removal. Rack storage, with its open flue spaces, can allow fire to climb quickly.

Aisles and flue spaces

Aisle widths support both firefighting and evacuation. Flue spaces within racks allow sprinkler water to reach burning goods and allow heat to rise to the ceiling where it activates sprinklers. When aisles are narrowed or flue spaces are blocked with stock, protection can be compromised.

The main elements of warehouse fire protection

Automatic sprinkler systems

Sprinklers are usually the backbone of warehouse fire protection. Their design, typically developed using referenced standards such as NFPA 13 within the framework set by the Saudi code, depends on commodity class, storage height, arrangement and building height. Depending on these factors, ceiling sprinklers alone may be sufficient, or in-rack sprinklers may be needed. The sprinkler system also determines the water supply and fire pump capacity, which can be significant cost items in an industrial facility.

Detection and alarm

Large open volumes and high roofs can delay detection. Detection technology and placement must suit the space, and alarm systems must be audible throughout noisy operational areas.

Smoke and heat removal

Smoke and heat venting, or mechanical smoke exhaust where required, helps firefighters see and approach a fire and limits heat damage to the structure. Its design must be coordinated with the sprinkler system so the two work together rather than against each other.

Compartmentation and separation

Fire walls and rated separations limit the area a single fire can affect. Offices, battery charging areas, hazardous material stores and production areas often need to be separated from bulk storage. In industrial facilities, process hazards may require additional separation or specialised protection.

Fire service access and water supply

Large buildings need adequate fire apparatus access roads, hydrants and entry points so that firefighters can reach the fire. These requirements affect site planning from the very first layout.

Process hazards in industrial facilities

Factories add a further layer of risk beyond storage. Processes may involve flammable liquids and gases, combustible dusts, high-temperature equipment, hot work or large electrical installations. Each needs to be identified and assessed during design, because the protection required, whether special suppression systems, explosion protection, ventilation, separation distances or hazardous area classification for electrical equipment, can shape the building layout and structure. A hazard review involving the owner's process engineers and the fire protection engineer at concept stage is far more effective than retrofitting protection once production lines have been installed.

Approvals and authorities

For most warehouses and industrial buildings, fire safety approvals and certificates are handled by the General Directorate of Civil Defense, with municipal permitting through Balady. Facilities that fall under the supervision of the Supreme Authority for Industrial Security (SAIS, formerly the High Commission for Industrial Security), such as certain energy, petrochemical and critical industrial sites, must also comply with that authority's safety and fire protection directives and approval process. Confirming early which regime applies avoids designing to the wrong set of requirements.

Where a proposed solution does not fit prescriptive requirements, for example an unusual storage configuration or an existing building being converted to storage use, a documented engineering judgment or performance-based justification may be appropriate, subject to the authority's formal acceptance.

The change-of-use trap

Many fire safety problems in industrial buildings arise not at design but later, when a building's use changes. A tenant brings in a different product, racking is raised to increase capacity, or a portion of the warehouse is converted to light manufacturing. Each change can alter the hazard classification and invalidate the original fire protection design. Owners and tenants should treat any change in commodity, storage height or layout as a trigger for a fire safety review. Aknan's fire and safety services include evaluation of existing facilities, inspection and testing of systems, and gap reports with practical recommendations.

Practical recommendations

  • Define the commodities, packaging and storage arrangement as precisely as possible before design, and allow for realistic future flexibility.
  • Design the sprinkler system, water supply and building height together, not in sequence.
  • Plan racking layouts with the fire protection engineer, including aisle widths and flue spaces.
  • Confirm early whether Civil Defense alone or SAIS requirements also apply.
  • Review fire protection whenever stored goods, storage height or layout change.

Conclusion

Warehouse and industrial fire safety design in Saudi Arabia succeeds when the fire protection is designed around the real storage operation and kept aligned with it over time. Clear information about commodities and storage at the outset, coordinated design of sprinklers, venting and compartmentation, and disciplined review when operations change will protect people, stock and business continuity.